Transformer Sizing Calculator
Standard kVA selection from load and growth margin, primary and secondary full-load amps, available fault current at the secondary with an AIC / SCCR check, and NEC 450.3(B) overcurrent protection.
BasisFLA = kVA·1000 / (√3·V) · Isc = FLA / %Z, infinite bus, %Z × 0.9 · OCPD per NEC 2023 Table 450.3(B), 240.6(A)
Frequently asked questions
How do you size a transformer?
Convert the load to kVA (kVA = kW / PF, or √3 × V × I / 1000 for three-phase), add a growth margin — 20 to 25 % is common — and pick the next standard kVA rating. Standard three-phase ratings are 15, 30, 45, 75, 112.5, 150, 225, 300, 500, 750, 1000, 1500, 2000 and 2500 kVA; single-phase ratings are 10, 15, 25, 37.5, 50, 75, 100, 167, 250, 333 and 500 kVA.
How is transformer full-load current calculated?
For three-phase, FLA = kVA × 1000 / (√3 × V_LL). For single-phase, FLA = kVA × 1000 / V. For example, a 225 kVA transformer at 480 V has a primary FLA of 270.6 A and at 208 V a secondary FLA of 624.5 A.
How is the available fault current at the secondary calculated?
Assuming an infinite (zero-impedance) utility source, the bolted three-phase fault current at the secondary terminals is Isc = FLA_secondary / (%Z / 100). This is the worst case for the transformer itself — the real value is lower once source and cable impedance are included. The calculator can also reduce %Z by 10 % to cover the nameplate impedance tolerance, which gives a conservative (higher) fault current for checking equipment interrupting ratings.
What does the AIC / SCCR check mean?
NEC 110.9 requires overcurrent devices to have an interrupting rating at least equal to the available fault current at their line terminals, and 110.10 requires equipment short-circuit current ratings (SCCR) to be coordinated with it. The calculator compares the fault current at the transformer secondary with the rating you enter for the secondary main or panelboard. 110.24 also requires the available fault current to be field-marked on service equipment in other than dwelling units.
How is transformer overcurrent protection sized under NEC 450.3(B)?
For transformers of 1000 V and less, Table 450.3(B) allows either primary-only protection at 125 % of primary FLA (167 % if the current is below 9 A, 300 % below 2 A), or primary protection up to 250 % combined with secondary protection at 125 % of secondary FLA. Where 125 % does not match a standard rating, Note 1 permits the next higher standard size. Secondary conductors also need protection under 240.21(C).