Voltage Drop Calculator — NEC 2023
AC voltage drop for feeders and branch circuits, 14 AWG to 1000 MCM, copper or aluminum. Pass-fail against the NEC 3 % and 5 % Informational Notes with minimum-size recommendation.
NEC 210.19 / 215.2 voltage-drop limits are Informational Notes — recommendations, not code-mandatory. Check your AHJ.
Frequently asked questions
What is a voltage drop calculation?
Voltage drop is the loss of voltage along a conductor due to its impedance. For NEC the formula isVd = b × I × L × Z / 1000 / setswith Z in ohms per 1000 ft. For IEC,Vd = b × (R cosφ + X sinφ) × I × L / 1000 / setswith R, X in mΩ/m and L in metres. b = 2 for single-phase and √3 (≈1.732) for three-phase.
Should I use NEC or IEC mode?
Use NEC for installations in the United States and jurisdictions that adopt NFPA 70 (typical voltages 120 / 208 / 240 / 277 / 480 / 600 V, conductors sized in AWG and MCM). Use IEC for projects that follow IEC 60364 or a national standard derived from it — most of Europe, the UK (BS 7671), Australia / New Zealand (AS/NZS 3000), and many parts of Asia and the Middle East. The typical IEC voltages are 230 V single-phase and 400 V three-phase, with conductors sized in mm².
Is the NEC 3 % / 5 % voltage drop limit mandatory?
No. The 3 % branch-circuit limit (NEC 210.19) and the 5 % combined feeder-plus-branch limit (NEC 215.2) are Informational Notes — recommendations, not code-mandatory rules. Check with your Authority Having Jurisdiction (AHJ) for local requirements.
What are the IEC voltage drop limits?
IEC 60364-5-52 Annex G suggests a maximum voltage drop of 3 % for lighting circuits and 5 % for other uses (appliances, motors, general purpose), measured from the origin of the installation to any point of utilisation. These are guidance values; national wiring regulations (for example BS 7671 in the UK) may impose stricter limits.
Which impedance data does this calculator use?
NEC mode uses NEC 2023 Chapter 9 Table 9 AC effective impedance, linearly interpolating between the 1.0 and 0.85 power-factor columns. IEC mode uses IEC 60364-5-52 reference values for R (at 70 °C) and X for PVC-insulated single-core cables under reference method C, combined as R cosφ + X sinφ.
Does the calculator account for temperature and installation method?
Only implicitly. Table 9 (NEC) and the IEC reference values assume typical operating temperatures (≈75 °C for NEC, 70 °C for IEC PVC) and representative cable geometries. Resistance rises roughly 0.4 % per °C above these baselines, and reactance can shift by 10 – 30 % for very different installations (for example widely-spaced single cores in free air vs. a tightly bundled multi-core cable). For high-stakes designs, apply the temperature and geometry corrections from the full tables rather than the simplified values used here.