What wire and breaker do I need for a 48 A EV charger?
60 A breaker. The wire depends on how you run it.
75 °C terminals
60 °C limit, 334.80
75 °C terminals
An EV charger is a continuous load (625.42), so the circuit is sized at 125 %: 48 A × 1.25 = 60 A (625.41). Ground: 10 AWG copper (Table 250.122). These are NEC 2023 figures; Canada’s CEC gives different answers.
Run your numbers in Cable SizingWhat the web says
16 top answers, checked Nov 18, 2026Every page gets the breaker right. The wire is where they split: most never say whether they mean conductors in conduit or NM cable, and that is the whole answer.
How we checked: the top-ranked web pages for this question on Nov 18, 2026, each read in full and scored on the same checklist. We describe wrong claims, not the sites that make them.
Why “6/2 Romex on 60 A” keeps coming up
6 AWG copper is 65 A at 75 °C, so it looks like enough. NM cable, though, is limited to the 60 °C ampacity (334.80), and 6 AWG at 60 °C is 55 A. That’s below the 60 A the charger circuit needs. The 90 °C insulation inside NM-B can be used for derating math, but the final ampacity is still capped at the 60 °C value.
Tesla and other makers list 6 AWG because their tables assume THHN in conduit. They aren’t wrong, they’re just assuming a different wiring method.
Smaller chargers
| Charger | Breaker ×1.25 | THHN Cu 75 °C | NM Cu 60 °C |
|---|---|---|---|
| 48 A | 60 A | 6 AWG | 4 AWG |
| 40 A | 50 A | 8 AWG | 6 AWG |
| 32 A | 40 A | 8 AWG | 8 AWG |
Long runs: when voltage drop takes over
48 A at 240 V, copper, PF 1.0, one-way length. A charger runs at full current for hours, so it’s worth staying under 3 %: extra drop means slower charging and more heat in the wire.
| Length | 6 AWG Cu | 4 AWG Cu | |
|---|---|---|---|
| 75 ft | 1.47 % | 0.93 % | 6 AWG fine |
| 100 ft | 1.96 % | 1.24 % | 6 AWG fine |
| 150 ft | 2.94 % | 1.86 % | 6 AWG just passes |
| 200 ft | 3.92 % | 2.48 % | use 4 AWG |
Common mistakes
- Sizing the breaker or wire at 48 A. The 125 % factor applies to both the breaker and the conductor’s terminal-column ampacity.
- Applying 125 % twice. Derating for ambient temperature or bundling is a separate check against the actual 48 A. Don’t multiply it by 1.25 again.
- 48 A through a NEMA 14-50. A 50 A receptacle tops out at 40 A of continuous charging, so a full 48 A charger has to be hardwired.
- Forgetting the service. A 60 A circuit is a big new load. Check whether the service can carry it (220.82 / 220.87), or use an energy management system (625.42(A)). See the Load Calculator.
- GFCI. Receptacles that supply EV chargers need GFCI protection (625.54). A hardwired charger has no receptacle; its personnel protection is built into the listed unit (625.22). The 2026 NEC extends 625.54 to hardwired outlets too, so check which edition your area uses.
Where people ask this
- Is #6 NM on a 60A breaker code compliant for a Tesla 48A (continuous load) EV charger? Mike Holt Forum
- Why does Tesla recommend such a small gauge wire for their chargers? DIY Stack Exchange
- 8/2 wire for 240 V EV charger DIY Stack Exchange
- Is this wire good for a 60 amp breaker, 48 A charging? r/evcharging
Questions are rephrased in our own words; Stack Exchange content is CC BY-SA and credited to the original authors. Every number on this page comes from the powercalc.tools calculators (NEC 2023 Table 310.16, Table 250.122, Chapter 9 Table 9). Not a substitute for your AHJ, the charger’s installation manual, or a licensed electrician. See Methodology.