Answer · EV charging

What wire and breaker do I need for a 48 A EV charger?

NEC 2023Numbers from our calculators16 web answers reviewed
Short answer

60 A breaker. The wire depends on how you run it.

THHN copper in conduit · 75 °C terminals
6 AWG
65 A
NM cable (Romex) · 60 °C limit, 334.80
4 AWG
6 AWG NM is only 55 A
Aluminum in conduit · 75 °C terminals
4 AWG Al
65 A

An EV charger is a continuous load (625.42), so the circuit is sized at 125 %: 48 A × 1.25 = 60 A (625.41). Ground: 10 AWG copper (Table 250.122). These are NEC 2023 figures; Canada’s CEC gives different answers.

Run your numbers in Cable Sizing

What the web says

16 top answers, checked Nov 18, 2026

Every page gets the breaker right. The wire is where they split: most never say whether they mean conductors in conduit or NM cable, and that is the whole answer.

16/16
give the right breaker: 60 A
7/16
give a wire size without saying which wiring method
6/16
explain why 6 AWG Romex isn’t enough for a 60 A circuit
1/16
quote a wrong ampacity for 6 AWG
You’ll read: “6 AWG is rated 75 A in the 75 °C column.”
Actually: 75 A is the 90 °C value. At 75 °C it’s 65 A, and terminals almost never allow 90 °C.
You’ll read: “Use 6 AWG for a 48 A charger.”
Actually: Only in conduit (THHN). In NM cable, 6 AWG is limited to 55 A, which is below the 60 A circuit, so you need 4 AWG.
You’ll read: “The next-size-up rule lets 6 AWG NM (55 A) go on a 60 A breaker.”
Actually: 240.4(B) is about protecting the wire. It doesn’t change how big the wire must be: for a 48 A continuous load the conductor itself needs 60 A of ampacity (210.19(A)(1), 625.42). 55 A isn’t enough.

How we checked: the top-ranked web pages for this question on Nov 18, 2026, each read in full and scored on the same checklist. We describe wrong claims, not the sites that make them.

Why “6/2 Romex on 60 A” keeps coming up

6 AWG copper is 65 A at 75 °C, so it looks like enough. NM cable, though, is limited to the 60 °C ampacity (334.80), and 6 AWG at 60 °C is 55 A. That’s below the 60 A the charger circuit needs. The 90 °C insulation inside NM-B can be used for derating math, but the final ampacity is still capped at the 60 °C value.

Tesla and other makers list 6 AWG because their tables assume THHN in conduit. They aren’t wrong, they’re just assuming a different wiring method.

Smaller chargers

ChargerBreaker ×1.25THHN Cu 75 °CNM Cu 60 °C
48 A60 A6 AWG4 AWG
40 A50 A8 AWG6 AWG
32 A40 A8 AWG8 AWG

Long runs: when voltage drop takes over

48 A at 240 V, copper, PF 1.0, one-way length. A charger runs at full current for hours, so it’s worth staying under 3 %: extra drop means slower charging and more heat in the wire.

Length6 AWG Cu4 AWG Cu
75 ft1.47 %0.93 %6 AWG fine
100 ft1.96 %1.24 %6 AWG fine
150 ft2.94 %1.86 %6 AWG just passes
200 ft3.92 %2.48 %use 4 AWG

Common mistakes

  • Sizing the breaker or wire at 48 A. The 125 % factor applies to both the breaker and the conductor’s terminal-column ampacity.
  • Applying 125 % twice. Derating for ambient temperature or bundling is a separate check against the actual 48 A. Don’t multiply it by 1.25 again.
  • 48 A through a NEMA 14-50. A 50 A receptacle tops out at 40 A of continuous charging, so a full 48 A charger has to be hardwired.
  • Forgetting the service. A 60 A circuit is a big new load. Check whether the service can carry it (220.82 / 220.87), or use an energy management system (625.42(A)). See the Load Calculator.
  • GFCI. Receptacles that supply EV chargers need GFCI protection (625.54). A hardwired charger has no receptacle; its personnel protection is built into the listed unit (625.22). The 2026 NEC extends 625.54 to hardwired outlets too, so check which edition your area uses.

Where people ask this

Questions are rephrased in our own words; Stack Exchange content is CC BY-SA and credited to the original authors. Every number on this page comes from the powercalc.tools calculators (NEC 2023 Table 310.16, Table 250.122, Chapter 9 Table 9). Not a substitute for your AHJ, the charger’s installation manual, or a licensed electrician. See Methodology.