The electrical questions people keep asking on forums, answered once: the NEC 2023 rule, numbers from our calculators, what the web gets wrong, and links back to where it was asked.
- Feeders
What size wire do I need for a 100 A subpanel?
3 AWG copper or 1 AWG aluminum at 75 °C, with an 8 AWG copper ground. Not 4 Cu / 2 Al — that is the 310.12 service table. Past about 140 ft at full load, voltage drop picks the wire. Worked numbers for 60–250 ft.
- Voltage drop
How long can a circuit be before voltage drop matters?
There is no fixed length. It depends on current, voltage and wire size. A loaded 20 A, 120 V circuit on 12 AWG passes 3 % at about 56 ft; a 30 A, 240 V circuit on 10 AWG goes about 125 ft. Table of common circuits.
- EV charging
What wire and breaker do I need for a 48 A EV charger?
60 A breaker. 6 AWG copper THHN in conduit, or 4 AWG copper if you use NM cable (Romex), because NM is limited to the 60 °C column. Voltage drop takes over past about 150 ft.