Answer · Voltage drop

How long can a circuit be before voltage drop matters?

NEC 2023Numbers from our calculators15 web answers reviewed
Short answer

No fixed length. Current × length decides.

120 V, 20 A circuit · 16 A on 12 AWG
~56 ft
to reach 3 %
240 V, 30 A circuit · 24 A on 10 AWG
~125 ft
to reach 3 %
240 V, 50 A circuit · 40 A on 6 AWG
~183 ft
to reach 3 %

Drop grows with current × length and shrinks with voltage and wire size. The 3 % / 5 % figures are recommendations, not code rules. What is enforceable is the equipment’s own minimum voltage: 110.3(B) makes the listed instructions a requirement.

Run your numbers in Voltage Drop

What the web says

15 top answers, checked Nov 18, 2026

Most pages get the 3 % / 5 % status right. None mention 110.3(B), the rule that makes an equipment maker’s minimum voltage enforceable, and a few give a length rule with no current or wire size attached.

12/15
say 3 % / 5 % are recommendations (Informational Notes)
1/15
call 3 % an NEC code requirement
0/15
mention 110.3(B) or the equipment’s minimum voltage
4/15
give a length rule of thumb without the current or wire size
1/15
mix up one-way and round-trip length
You’ll read: “Any run over 100 feet needs a voltage drop calculation.”
Actually: Length alone doesn’t tell you. 16 A on 12 AWG at 120 V reaches 3 % at about 56 ft; 8 A on the same wire goes about 112 ft. Current and wire size decide.
You’ll read: “Code requires voltage drop under 3 %.”
Actually: The 3 % / 5 % figures are Informational Notes in 210.19(A) and 215.2(A) — recommendations. Your AHJ, an energy code or the equipment instructions (110.3(B)) can make a limit mandatory.
You’ll read: “Enter the round-trip length.”
Actually: Calculators and the NEC formula take the one-way length. The ×2 for the return conductor is already in the formula.

How we checked: the top-ranked web pages for this question on Nov 18, 2026, each read in full and scored on the same checklist. We describe wrong claims, not the sites that make them.

Common circuits: where 3 % and 5 % are crossed

Copper, NEC Chapter 9 Table 9, PF 1.0. The load is 80 % of the breaker rating, a typical heavy steady load. Length is one-way. At half the load, the length doubles.

CircuitLoadWire3 % at5 % at
120 V, 15 A12 A14 AWG~48 ft~81 ft
120 V, 20 A16 A12 AWG~56 ft~94 ft
240 V, 30 A24 A10 AWG~125 ft~208 ft
240 V, 50 A40 A6 AWG~183 ft~306 ft

The same current on the same wire at 240 V goes twice as far as at 120 V, because the same volts lost are half the percentage.

Is 3 % a code requirement?

No. The 3 % branch-circuit and 5 % feeder-plus-branch figures are Informational Notes in 210.19(A) and 215.2(A). Some exceptions:

  • Your AHJ, or an energy code, can make them mandatory. Some commercial energy codes do.
  • Equipment instructions can. Motors, EV chargers, well pumps and LED drivers often list a minimum voltage. 110.3(B) makes the listed instructions enforceable.
  • A failing drop is a design problem even when it’s legal. Motors run hotter, chargers charge slower, and lights dim when big loads start.

Common mistakes

  • Entering the breaker size as the load. A 100 A breaker does not mean 100 A of load. At 150 ft, 3 AWG copper drops 3.13 % at 100 A but 1.41 % at a 45 A load.
  • Using round-trip length. The calculators (and the NEC formula) take one-way length.
  • Upsizing the breaker to fix voltage drop. Upsize the wire, keep the breaker. Then upsize the equipment ground in proportion (250.122(B)).
  • Ignoring motor starting. A compressor or pump draws several times its running current for a moment. Steady-state 3 % can mean a 10 %+ dip at start.

Where people ask this

Questions are rephrased in our own words; Stack Exchange content is CC BY-SA and credited to the original authors. Every number on this page comes from the powercalc.tools voltage drop calculator (NEC 2023 Chapter 9 Table 9, steel conduit; PVC gives an equal or slightly lower drop). Not a substitute for your AHJ or a licensed electrician. See Methodology.