What size wire do I need for a 100 A subpanel?

NEC 2023Numbers from our calculators16 web answers reviewed
Short answer

3 AWG copper or 1 AWG aluminum. Not 4 Cu / 2 Al.

Copper · 75 °C column, 310.16
3 AWG
100 A · ground 8 AWG
Aluminum · 75 °C column, 310.16
1 AWG Al
100 A · ground 6 AWG Al
Long run at full load · voltage drop decides
> 140 ft
3 AWG Cu hits 3 % at ~144 ft

A 100 A feeder breaker needs conductors rated at least 100 A in the 75 °C column of NEC Table 310.16. The 4 AWG Cu / 2 AWG Al sizes come from the 83 % dwelling table in 310.12, which applies only to the service and the main feeder carrying the whole house — not to a subpanel feeder.

Run your numbers in Cable Sizing

What the web says

16 top answers, checked Nov 18, 2026

Most pages get the size right, and half of them warn against the 310.12 shortcut. But the top-ranked result for this question gives the wrong answer, and the #2 aluminum mistake shows up even on pages that are otherwise correct.

12/16
give a wire size that actually carries 100 A at 75 °C
4/16
use the 83 % dwelling rule (310.12) for a subpanel
7/16
say #2 aluminum (2-2-2-4) is fine on a 100 A breaker
14/16
mention voltage drop or run length
10/16
say to keep neutral and ground separate at the subpanel
You’ll read: “A 100 A subpanel needs 4 AWG copper or 2 AWG aluminum.”
Actually: Those are the 310.12 sizes for a dwelling service, sized at 83 %. A subpanel feeder carries its full rating: 3 AWG Cu or 1 AWG Al.
You’ll read: “2-2-2-4 aluminum is 100 A cable.”
Actually: #2 Al is 90 A at 75 °C, and 90 A is itself a standard breaker size, so 240.4(B) can’t round it up. The largest breaker on #2 Al is 90 A.
You’ll read: “Adding a subpanel adds capacity.”
Actually: It adds breaker spaces, not amps. The service still has to carry the total calculated load.

How we checked: the top-ranked web pages for this question on Nov 18, 2026, each read in full and scored on the same checklist. We describe wrong claims, not the sites that make them.

How the length changes the answer

100 A load at 240 V single-phase, PF 1.0, target ≤ 3 % drop. The size listed is the larger of the ampacity size and the voltage-drop size.

One-way lengthCopperDropAluminumDrop
60 ft3 AWG1.25 %1 AWG1.25 %
100 ft3 AWG2.08 %1 AWG2.08 %
150 ft2 AWG2.50 %1/02.50 %
200 ft1 AWG2.67 %2/02.67 %
250 ft1/02.50 %3/02.71 %

If the hots are upsized for voltage drop, the equipment ground has to be upsized in the same proportion (250.122(B)).

Use the load you expect, not the breaker

A 100 A breaker does not mean 100 A of load. Most garage and shop subpanels carry far less, so check voltage drop at the calculated or expected load.

At 150 ft, 3 AWG copper drops 3.13 % at 100 A but only 1.88 % at 60 A. Sized for voltage drop at 100 A, the run needs 2 AWG; at a realistic 60 A it doesn’t. Ampacity still has to match the breaker either way.

Common mistakes

  • Using the 83 % dwelling rule (310.12) on a subpanel feeder. 310.12 covers only the service conductors and the main feeder that carries a dwelling’s entire load.
  • #2 aluminum (as in 2-2-2-4) on a 100 A breaker. #2 Al is 90 A at 75 °C. The “next size up” rule in 240.4(B) only applies when the ampacity falls between standard sizes, and 90 A is a standard size. For a true 100 A feeder use 1 AWG Al or 3 AWG Cu.
  • Thinking SER cable indoors drops to the 60 °C column. It doesn’t. 338.10(B)(4) applies the NM installation rules to interior SE cable but excludes 334.80, so SER keeps its 75 °C ampacity at these sizes.
  • Three wires to a detached garage. A feeder to a separate building needs four conductors: two hots, a neutral and an equipment ground. The neutral stays isolated from the ground at the subpanel (250.32(B)), and the building needs its own grounding electrode (250.32(A)).
  • Checking only the 90 °C column. THHN is rated 90 °C, but breaker and panel lugs are usually rated 75 °C (110.14(C)). Unmarked terminals on circuits of 100 A or less default to the 60 °C column (110.14(C)(1)(a)).

Where people ask this

Questions are rephrased in our own words; Stack Exchange content is CC BY-SA and credited to the original authors. Every number on this page comes from the powercalc.tools calculators (NEC 2023 Table 310.16, Table 250.122, Chapter 9 Table 9). Not a substitute for your AHJ or a licensed electrician. See Methodology.