What size wire do I need for a 100 A subpanel?
3 AWG copper or 1 AWG aluminum. Not 4 Cu / 2 Al.
75 °C column, 310.16
75 °C column, 310.16
voltage drop decides
A 100 A feeder breaker needs conductors rated at least 100 A in the 75 °C column of NEC Table 310.16. The 4 AWG Cu / 2 AWG Al sizes come from the 83 % dwelling table in 310.12, which applies only to the service and the main feeder carrying the whole house — not to a subpanel feeder.
Run your numbers in Cable SizingWhat the web says
16 top answers, checked Nov 18, 2026Most pages get the size right, and half of them warn against the 310.12 shortcut. But the top-ranked result for this question gives the wrong answer, and the #2 aluminum mistake shows up even on pages that are otherwise correct.
How we checked: the top-ranked web pages for this question on Nov 18, 2026, each read in full and scored on the same checklist. We describe wrong claims, not the sites that make them.
How the length changes the answer
100 A load at 240 V single-phase, PF 1.0, target ≤ 3 % drop. The size listed is the larger of the ampacity size and the voltage-drop size.
| One-way length | Copper | Drop | Aluminum | Drop |
|---|---|---|---|---|
| 60 ft | 3 AWG | 1.25 % | 1 AWG | 1.25 % |
| 100 ft | 3 AWG | 2.08 % | 1 AWG | 2.08 % |
| 150 ft | 2 AWG | 2.50 % | 1/0 | 2.50 % |
| 200 ft | 1 AWG | 2.67 % | 2/0 | 2.67 % |
| 250 ft | 1/0 | 2.50 % | 3/0 | 2.71 % |
If the hots are upsized for voltage drop, the equipment ground has to be upsized in the same proportion (250.122(B)).
Use the load you expect, not the breaker
A 100 A breaker does not mean 100 A of load. Most garage and shop subpanels carry far less, so check voltage drop at the calculated or expected load.
At 150 ft, 3 AWG copper drops 3.13 % at 100 A but only 1.88 % at 60 A. Sized for voltage drop at 100 A, the run needs 2 AWG; at a realistic 60 A it doesn’t. Ampacity still has to match the breaker either way.
Common mistakes
- Using the 83 % dwelling rule (310.12) on a subpanel feeder. 310.12 covers only the service conductors and the main feeder that carries a dwelling’s entire load.
- #2 aluminum (as in 2-2-2-4) on a 100 A breaker. #2 Al is 90 A at 75 °C. The “next size up” rule in 240.4(B) only applies when the ampacity falls between standard sizes, and 90 A is a standard size. For a true 100 A feeder use 1 AWG Al or 3 AWG Cu.
- Thinking SER cable indoors drops to the 60 °C column. It doesn’t. 338.10(B)(4) applies the NM installation rules to interior SE cable but excludes 334.80, so SER keeps its 75 °C ampacity at these sizes.
- Three wires to a detached garage. A feeder to a separate building needs four conductors: two hots, a neutral and an equipment ground. The neutral stays isolated from the ground at the subpanel (250.32(B)), and the building needs its own grounding electrode (250.32(A)).
- Checking only the 90 °C column. THHN is rated 90 °C, but breaker and panel lugs are usually rated 75 °C (110.14(C)). Unmarked terminals on circuits of 100 A or less default to the 60 °C column (110.14(C)(1)(a)).
Where people ask this
- What wire gauge do I need for a 100 A subpanel at the end of a 60 ft run? DIY Stack Exchange
- What size wire should I use to feed a subpanel in my garage? DIY Stack Exchange
- Can I connect a 100 A subpanel to a 100 A main panel? DIY Stack Exchange
- What size breaker and wire do I need for a subpanel in my shed? DIY Stack Exchange
- Wire sizing for sub panel r/AskElectricians
Questions are rephrased in our own words; Stack Exchange content is CC BY-SA and credited to the original authors. Every number on this page comes from the powercalc.tools calculators (NEC 2023 Table 310.16, Table 250.122, Chapter 9 Table 9). Not a substitute for your AHJ or a licensed electrician. See Methodology.